WDZ-KYJYP2 Low smoke halogen-free flame retardant control cable
- Tel:+86-0550-7516689
- Fax:0550-7513058
- Mail:ahhl@ahhonglin.com
Description
Wdz-kyjyp2 low smoke halogen free flame retardant control cable
This product is suitable for AC 50-60Hz, rated voltage 750V and below, low smoke, halogen-free, non-toxic, non-corrosive (pollution-free cable) flame-retardant requirements as control and monitoring loop
1、 Production standard
Adopt enterprise standard and refer to gb9330-88
2、 Technical performance
The product is designed according to iec227, iec1034 and iec332 international standards
3、 Performance requirements
(1) bunching combustion type A or B, (height of carbonization part): ≤ 2.5m
(2) no delay burning (unburned distance): ≥ 50mm
(3) smoke intensity (* * small light transmittance) ≥ 60%
(4) HCl content ≤ 0.5mg/g
4、 Model name
model | Cable name |
DWZ-KVV | Copper core low smoke halogen free polyolefin insulated and sheathed flame retardant control cable |
DWZ-KVVP | Copper core low smoke halogen free polyolefin insulated and sheathed braided shielded flame retardant control cable |
DWZ-KVVP2 | Copper core low smoke halogen free polyolefin insulated and sheathed copper tape shielded flame retardant control cable |
DWZ-KVV22 | Copper core low smoke halogen free polyolefin insulated and sheathed steel strip armored flame retardant control cable |
DWZ-KVVR | Copper core low smoke halogen free polyolefin insulated and sheathed flame retardant control flexible cable |
DWZ-KVVRP | Copper core low smoke halogen free polyolefin insulated and sheathed textile shielding flame retardant control flexible cable |
DWZ-KVVP2-22 | Copper core low smoke halogen-free polyolefin insulated and sheathed copper tape shielded steel strip armored flame retardant control cable |
WDZ-KYJY | Copper core XLPE insulated polyolefin sheathed halogen free low smoke flame retardant control cable |
WDZ-KYJYP | XLPE insulated steel tape armored halogen free low smoke class A (B or C) flame retardant power cable |
WDZ-KYJYP2 | AC PE insulated fine steel wire armored halogen free low smoke class A (B or C) flame retardant power cable |
WDZ-KYJYP3 | Copper core XLPE insulated polyolefin sheathed aluminum plastic composite tape shielded halogen free low smoke flame retardant control cable |
WDZ-KYJY23 | Copper core XLPE insulated polyolefin sheathed steel strip armored halogen free low smoke flame retardant control cable |
WDZ-KYJYP2/23 | Copper core XLPE insulated polyolefin sheathed copper tape shielded steel strip armored halogen free low smoke flame retardant control cable |
WDZ-KYJYP3/23 | Copper core XLPE insulated polyolefin sheathed aluminum plastic composite belt shielded steel strip armored halogen free low smoke flame retardant control cable |
"Wdz": low smoke halogen free flame retardant
5、 Cable specification
model | Nominal conductor cross section (mm2) | |||||||
zero point five | zero point seven five | one | one point five | two point five | four | six | ten | |
Number of cores | ||||||||
DWZ-KVV | - | 2~61 | 2~14 | 2~10 | ||||
DWZ-KVV2 | - | 4~61 | 4~14 | 4~10 | ||||
DWZ-KVV22 | - | 7~61 | 4~61 | 4~14 | 4~10 | |||
DWZ-KVVR | - | 4~61 | - | - | ||||
DWZ-KVVRP | - | 4~61 | 4~48 | - | - |
Note: the recommended core number series are: 2, 3, 4, 5, 7, 8, 10, 12, 14, 16, 19, 24, 27, 30, 44, 48, 52 and 61 cores.
6、 Delivery requirements
(1) when the circle is 100m, the coil should be larger than 100m;
(2) according to the agreement between the supplier and the supplier, any length delivery is allowed, and the length measurement error is ± 0.5%