Mining rubber sheathed flexible cable
- Tel:+86-0550-7516689
- Fax:0550-7513058
- Mail:ahhl@ahhonglin.com
Description
1、 Product features and uses
This product is applicable to mine mobile electrical equipment, mining machinery, lifting and conveying machine, etc. it is used as power connection line for AC 50 Hz, rated voltage 6 kV and below.
2、 Product execution standard
This product performs Mt 818.1-818.14-1999 standard
3、 Usage features
1. The rated voltage U0 / u is 0.3/6kv;
2. Long term allowable working temperature of Conductor: - 45 -- 90 ℃;
3. Small bending radius of cable: not less than 6 times of cable outer diameter.
4、 Product model and name
| Type number | Product name | How to use it |
| MC-0.38/0.66 | Rubber sheathed flexible cable for Shearer | Power connection of shearer and similar equipment with rated voltage of 0.38/0.66kv |
| MCP-0.38/0.66 | Shield rubber sheathed flexible cable for Shearer | Power connection of shearer and similar equipment with rated voltage of 0.38/0.66kv |
| MCP-0.66/1.14 | Shield rubber sheathed flexible cable for Shearer | Power connection of shearer and similar equipment with rated voltage of 0.66/1.14kv |
| MCP-1.9/3.3 | Shield rubber sheathed flexible cable for Shearer | Power connection of shearer and similar equipment with rated voltage of 1.9/3.3kv |
| MCPT-1.9/3.3 | Shield rubber sheathed flexible cable for Shearer | Power connection of shearer and similar equipment with rated voltage of 1.9/3.3kv |
5、 Main technical indicators
| Nominal cross sectional area of conductor mm2 | Insulation resistance at 20 ℃ m Ω / km | |
| MCP0. 66 / 1.14kv and below | MCP1. 9/3.3KV | |
| sixteen | ≥120 | - |
| twenty-five | ≥120 | - |
| thirty-five | ≥100 | ≥380 |
| fifty | ≥100 | ≥350 |
| seventy | ≥80 | ≥320 |
| ninety-five | ≥80 | ≥280 |
| Control core | ≥100 | ≥100 |
The company can design and manufacture various specifications and models of wires and cables according to the needs of customers!
6、 Cable specification and performance
| model | Number of cores × Conductor cross section (mm2) | Insulation thickness of power core mm | Sheath thickness mm | Cable outer diameter (mm) | |||
| Power cord | Earth core | Control core | ***Small value | ***Large value | |||
| MC-0.38/0.66 | three × sixteen | one × four | three × two point five | one point six | four point five | thirty-one point three | thirty-five point one |
| three × twenty-five | one × six | four × two point five | one point eight | five point five | thirty-seven point eight | forty-two | |
| three × thirty-five | one × six | four × four | one point eight | five point five | forty-one point eight | forty-six | |
| three × fifty | one × ten | seven × four | two | five point five | forty-six | fifty point nine | |
| MCP-0.38/0.66 | three × sixteen | one × four | three × two point five | one point six | four point five | thirty-four point seven | thirty-eight point five |
| three × twenty-five | one × six | four × two point five | one point eight | five point five | forty-one point three | forty-five point five | |
| three × thirty-five | one × six | four × four | one point eight | five point five | forty-five point one | forty-nine point three | |
| three × fifty | one × ten | seven × four | two | five point five | fifty | fifty-four point three | |
| MCP-0.66/1.14 | three × thirty-five | one × six | three × six | two | six | forty-seven point two | fifty-one point four |
| three × fifty | one × ten | three × six | two point two | seven | fifty-four point three | fifty-eight point six | |
| three × seventy | one × sixteen | three × six | two point two | seven | fifty-nine point six | sixty-four point three | |
| three × ninety-five | one × twenty-five | three × ten | two point four | seven | sixty-four point five | seventy point one | |
| Number of cores × Conductor cross section (mm2) | Power cord insulation Nominal thickness | Nominal thickness of sheath mm | Cable outer diameter mm | ||||||
| MCP-1.9/3.3 (type A) | MCP-1.9/3.3 (type b) | ||||||||
| Power cord | Earth core | Control core | mm | Type A | Type B | ***Small value | ***Large value | ***Small value | ***Large value |
| three × sixteen | one × four | three × two point five | two point eight | six | seven | fifty-two point one | fifty-six point eight | sixty | sixty-three |
| three × twenty-five | one × six | four × two point five | two point eight | seven | seven point five | fifty-six point four | sixty-two | sixty-three point eight | seventy point two |
| three × thirty-five | one × six | four × four | three | seven | seven point five | sixty-two point seven | sixty-nine | sixty-nine | seventy point two |
| three × fifty | one × ten | seven × four | three | seven | seven point five | sixty-seven point eight | seventy-four point six | seventy-three point one | seventy-eight |
| Number of cores × Conductor cross section (mm2) | Power cord insulation Nominal thickness | Nominal sheath thickness | Cable outer diameter mm | ||
| MCPT-1.9/3.3 | |||||
| Power cord | Earth core | mm | mm | ***Small value | ***Large value |
| three × thirty-five | one × sixteen | two point eight | six | fifty-five | sixty point seven |
| three × fifty | one × twenty-five | two point eight | six | fifty-seven point eight | sixty-three |
| three × seventy | one × thirty-five | three | six | sixty-four point one | seventy point eight |
| three × ninety-five | one × fifty | three | six | sixty-nine point two | seventy-six point two |
The company can design and manufacture various specifications and models of wires and cables according to the needs of customers!