Detailed description of structure of low smoke halogen free cable
The cable insulation is usually made of halogen-free flame retardant polyolefin and silicone rubber, and the sheath is usually made of thermosetting or thermoplastic low smoke halogen-free flame retardant polyolefin material. Insulation and sheath materials for low smoke halogen free flame retardant cables
At present, hydrated metal oxides are mostly used as flame retardant fillers.
It is suitable for 600 / 1000V and below power, household appliances, all kinds of mobile electrical equipment and tools.
Detailed description of low smoke halogen free cable structure
1 General requirements for cable construction
1.1 Conductor: annealed copper wire. Unless otherwise specified in the product process, each single wire in the conductor can be tinned or tinned copper wire. Tinned copper wire shall be covered with an effective tin layer.
1.1.1 structure
The conductor structure shall comply with GB / t3956 standard.
Cross sectional area mm2 | DC resistance of conductor ≤ Ω / km at 20 ℃ | Cross sectional area mm2 | DC resistance of conductor ≤ Ω / km at 20 ℃ | ||
No tin plating | Tin plating | No tin plating | Tin plating | ||
one | nineteen point five | twenty | sixteen | one point two one | one point two four |
one point five | thirteen point three | thirteen point seven | twenty-five | zero point seven eight zero | zero point seven nine five |
two point five | seven point nine eight | eight point two one | thirty-five | zero point five five four | zero point five six five |
four | four point nine five | five point zero nine | fifty | zero point three eight six | zero point three nine three |
six | three point three zero | three point three nine | seventy | zero point two seven two | zero point two seven seven |
ten | one point nine one | one point nine five | |||
1.2 insulation
1.2.1 the insulation shall be thermoplastic halogen-free low smoke flame retardant 90 ℃ cable material.
1.2.2 the insulation shall be tightly packed on the conductor.
1.2.3 thickness
The average value of insulation thickness shall not be less than the specified value specified in this process, but the thickness at any point can be less than the specified value, as long as it is not less than 90% - 0.1 of the specified value.
1.2.4 the insulation thickness and outer diameter shall meet the requirements in the table below
Cross sectional area mm2 | Nominal thickness mm | Upper limit of average outer diameter mm | Cross sectional area mm2 | Nominal thickness mm | Upper limit of average outer diameter mm |
one | zero point seven | two point nine | sixteen | one | eight |
one point five | zero point seven | three point three | twenty-five | one point two | nine point eight |
two point five | zero point eight | three point nine | thirty-five | one point two | eleven |
four | zero point eight | four point four | fifty | one point four | thirteen |
six | zero point eight | four point nine | seventy | one point four | fifteen |
ten | one | six point eight |
Detailed description of low smoke halogen free cable structure
2. The mechanical and physical properties of thermoplastic low smoke halogen-free cable material shall meet the requirements of.
Mechanical and physical properties of thermoplastic low smoke halogen free cable compound
Serial number | Test items | Company | performance requirement | test method |
one one point one
one point two
two two point one
two point two
two point three
three
four five six
| Mechanical properties before aging Original value of tensile strength ----***Small median Original value of elongation at break ----***Small median Mechanical properties after air aging Aging conditions - temperature -----Processing time Tensile strength after aging ----***Small median ----***Large rate of change Elongation after aging ----***Small median ----***Large rate of change Smoke density flameless There are some Oxygen index Halogen acid gas content PH value Conductivity |
N/mm2 %
℃ h
N/mm2 %
% %
-- -- % Mg/g -- Us/mm |
≥9.0 ≥150
100±2 one hundred and sixty-eight
≥9.0 ±30
≥120 ±30
≤250 ≤100 ≥30 ≤5 ≥4.3 ≤10 |
GB/T2951. eleven
GB/T8323
GB/T2406 GB/T17650. one |
Detailed description of low smoke halogen free cable structure
See table for electrical performance
Rated voltage U0 / u | 600/1000V | 450/750 |
Test voltage / kV | three point five | two point five |
Time / min | five | five |
3 packaging, transportation and storage
3.1 packaging
3.1.1 cable products shall be packaged in coils or in coils. The cable reels for reel installation shall comply with the provisions in JB / t8137. In order to prevent damage to the products during storage and transportation, appropriate protection shall be added.
3.1.2 the distance between the outer layer of the coiled cable and the connecting edge of the side plate of the cable tray shall not be less than 60mm. Both ends of the cable shall be sealed and fixed on the cable reel.
3.1.3 the looped products shall be coated with banded materials with certain strength and bound firmly.
3.2 transportation
Cable transportation shall meet the following requirements:
The cable reel shall not be placed horizontally;
Long distance rolling is not allowed;
No impact, crush and any mechanical damage;
It is not allowed to be affected by damp and exposed to the sun for a long time during long-distance transportation.
3.3 storage
Cable storage shall meet the following requirements:
Do not place the cable reel in the horizontal position;
Moistureproof and sun proof;
Prevent extrusion deformation and any mechanical damage.