Flexible intrinsically safe shielded high temperature resistant cable
- Tel:+86-0550-7516689
- Fax:0550-7513058
- Mail:ahhl@ahhonglin.com
Description
1、 Executive standard: Q / tat7689
2、 Purpose: This cable is intrinsically safe, also known as intrinsically safe cable. It has low capacitance and low inductance, excellent shielding performance and anti-interference performance, so its explosion-proof performance is better than general computer cable and control cable. It is suitable to be used as transmission line in circuits such as distributed system and automatic detection and control system in occasions with explosion-proof requirements, and has super flexibility, high temperature resistance and other properties.
3、 Usage characteristics:
Rated voltage uo / u: 300 / 500V
Maximum working temperature: not more than 70 ℃ for general type
The maximum temperature of the rear belt of the model shall not exceed 105 ℃
Minimum ambient temperature: fixed laying: - 40 ℃, non fixed laying: - 15 ℃
Minimum bending radius: the cable without armor layer shall not be less than 6 times of the outer diameter of the cable
The armored cable shall not be less than 12 times of the outer diameter of the cable
4、 Main technical indicators:
Technical indicators of the project unit
PE insulation PVC insulation
Working capacitance (core core) (1kHz) ≤ PF / M 90 180
Capacitance unbalance (1kHz) ≤ PF / M 1/
Distributed inductance ≤ μ H/m 0.6 0.6
Inductance resistance ratio ≤ 0.5mm2 μ H/Ω 20 20
0.75mm2
1.0mm2 25 25
1.5mm2 35 35
Anti interference of external magnetic field (400A / M) ≤ MV 5
Antistatic induction (20kV) ≤ MV 80
Anti RF interference (120dB) 60 dB
Insulation resistance (20) ℃ m Ω. Km 5000 25
Test voltage V / 1min 1000
The flame retardancy meets the requirements of gb12666-90