Flame retardant control cable for coal mine
- Tel:+86-0550-7516689
- Fax:0550-7513058
- Mail:ahhl@ahhonglin.com
Description

1. Product use
The flame retardant control cable for coal mine is suitable for fixed and mobile flame retardant control, monitoring circuit and protection circuit for coal mine with rated voltage of 450 / 750V and below. It can be used as the control wiring between electrical equipment in coal mine.
2. Executive standard: Q / zs7-2008 flame retardant control cable for coal mine
3. Service characteristics
3.1 rated voltage U0 / u: 450 / 750V
3.2 long term working temperature of cable conductor: 70 ℃ for PVC insulation.
: 90 ℃ for XLPE insulation.
In case of short circuit (* * long duration no more than 5 s), high temperature of cable conductor shall not exceed 160 ℃ for PVC insulation and 250 ℃ for XLPE insulation
3.3 the temperature of cable laying shall not be lower than 0 ℃.
3.4 recommended allowable bending radius
The cable without armor layer shall not be less than 6 times of cable outer diameter.
The cable with armored layer or copper tape shielding structure shall not be less than 12 times of the outer diameter of the cable.
Flexible cable with shielding layer structure shall not be less than 6 times of cable outer diameter.
4. Cable model and name
Type number | Name | Main application scope |
MKVV | PVC (XLPE) insulated PVC sheathed control cable for coal mine | It is used in the control circuit, monitoring circuit and protection circuit of coal mine, where flame retardant is required. |
MKVVP | PVC (XLPE) insulated PVC sheathed braided shielded control cable for coal mine | It is used in the control circuit, monitoring circuit and protection circuit of coal mine, which requires shielding and flame retardant. |
MKVVP2 | PVC insulated PVC sheathed copper tape shielded control cable for coal mine | It is used in the control circuit, monitoring circuit and protection circuit of coal mine, which requires shielding and flame retardant. |
MKVV22 | PVC (XLPE) insulated PVC sheathed steel strip armored control cable for coal mine | It can be used in the control circuit, monitoring circuit and protection circuit of coal mine, and can withstand large mechanical external force and flame retardant fixed occasions. |
MKVV32 | PVC insulated PVC sheathed fine steel wire armored control cable for coal mine | It can be used in coal mine control circuit, monitoring circuit and protection circuit, and can withstand large mechanical tension and flame retardant fixed occasions. |
MKVVP22 | PVC (XLPE) insulated PVC sheathed braided shielded steel strip armored control cable for coal mine | It can be used in the control circuit, monitoring circuit and protection circuit of coal mine, and can withstand large mechanical external force and shield flame retardant fixed occasions. |
MKVVP2- 22 | PVC (XLPE) insulated PVC sheathed copper tape shielded steel strip armored control cable for coal mine | It can be used in the control circuit, monitoring circuit and protection circuit of coal mine, and can withstand large mechanical external force and shield flame retardant fixed occasions. |
MKVVP2- 32 | PVC (XLPE) insulated PVC sheathed copper tape shielded fine steel wire armored control cable for coal mine | Control circuit for coal mine. Monitoring circuit and protection circuit can withstand large mechanical tension and flame retardant fixed occasions. |
MKVVR | PVC insulated PVC sheathed control flexible cable for coal mine | It is used in the control circuit, monitoring circuit and protection circuit of coal mine, where flame retardant is required. |
MKVVRP | PVC insulated PVC sheathed braided shielded control flexible cable for coal mine | It is used in the control circuit, monitoring circuit and protection circuit of coal mine, which requires shielding and flame retardant mobile occasions. |
5. Cable specification and scope
Table 2 cable specifications
Type number | Nominal section mm2 | ||||||
zero point seven five | one | one point five | two point five | four | six | ten | |
Number of cores | |||||||
MKVV MKYJV | 2~61 | 2~14 | 2~ 10 | ||||
MKVVP MKYJVP | 2~61 | 2~14 | 2~10 | ||||
MKVVP2 MKYJVP2 |
2~61 |
2~14 |
2~10 | ||||
MKVV22 MKYJV22 | 5~61 | 4~61 | 3~61 | 2~61 | 2~14 | 2~10 | |
MKVV32 MKYJV32 | 3~61 | 2~61 | 2~61 | 2~61 | 2~14 | 2~10 | |
MKVVP22 MKYJVP22 |
3~61 |
2~61 |
2~6l |
2~61 |
2~14 |
2~10 | |
MKVVR | 2~61 | 2~14 | 2~10 | ||||
MKVVRP | 2~61 | 2~14 | 2~10 | ||||
Note: the recommended core number series are 2, 3, 4, 5, 6, 7, 8, 10, 12, 14, 16, 19, 24, 27, 30, 37, 44, 48, 52, and 61 cores.